ERROR Code 205

ERROR Code 205

Detected LON traffic from unexpected Subnets at LonConnectionServer -> StyxLonConverter might be connected to wrong segment.
Important

The CU951 / M95 LON Monitor and all LON Targets must be predefined with the lane number at the device itself.

Initial installation

Check for correct setting of the lane number at the CU951 / M95 Monitordisplay and at the Lane Number Switches at the target. See installation manual for help.

Configured system

If the error code 205 appears with a configured system, check

  • whether CU951 / M95 LON Monitor or LON Target where swapped or replaced
  • whether have every CU951 / M95 LON Monitor or LON Target the correct lane number
  • whether the CU951 / M95 LON Monitor or LON Target is connected to the correct segment (STYX to LON Converter)